Beemet Watt meters are available in Single Phase, 3-Phase balanced load 3 or 4 wire, and 3-phase unbalanced load 3 or 4 wire configurations. They are used to indicate import – export (reverse – forward) power flow. These can be utilized on both sinusoidal and non-sinusoidal currents.
These meters are designed to an internationally accepted standard. The dimensions comply with the requirements of DIN 43700 and scales with DIN 43802. The performance confirms to IS 1248-83/93. The cases are made of ABS plastic material which has high tracking index for maximum electrical strength and safety.
Accuracy | ±1.5 / 2.0 of FSD |
Measurable Quantities | Active and Reactive Power |
Pointer deflection | 0 - 90º |
Input | Full-scale power value Pw or Pb |
Feasibility factor | "Lambda"=Pw/Ps or Pb / Ps |
Power factor | Cosφ = 1 ± 0.01 for Watt meters & Sinφ = 1 ± 0.01 for Var meters |
Voltage | Rated voltage + 2% |
Frequency | 45-65 Hz (50 Hz ±0.1% for E1B) |
Current | 20% to 120% of rated current |
Overload Capacity | According to IS: 1248 / IEC 51 |
Short duration | 2 times rated voltage for 5s: 1 overload 10 times rated current for 5s: 1 overload |
Continiously | 1.2 times rated voltage or current |
Operating Temperature | -10 to 55°C |
Storage Temperature | -25 to 65°C |
Relative Humidity | < 75% annaul average, non-condensing |
Model | Description | Current( Amp ) | Voltage( volt ) |
---|---|---|---|
WA-96, 144 | 1 Phase 1 Element | 1, 5, 10 | 63.5, 230 |
WA-96, 144 | 3 Phase 1 Element Balanced Load only |
1, 5, 10 | 110, 440 |
WA-96, 144 | 3 Phase 2 Element [3 Wire] Balanced or Unbalanced Load |
1, 5 | 110, 440 |
WA-96, 144 | 3 Phase 3 Element [4 Wire] Balanced or Unbalanced Load |
1, 5 | 110/ 3, 440/3 |