Frequency Meters

Beemet Frequencey meters are used to measure the applied frequency. They come as Pointer Type with built in Trasducer and Vibrating Reed Type.

Salient Features

  • Vibrating Reed Type Frequency meters indicate the supply frequency by means of individual reeds, when rated voltage+ 20% is applied across the terminals of the meter, the particular reed, whose natural frequency of vibration coincides with the supply frequency, vibrates with full amplitude. In case the supply frequency falls midway between two reeds both the reeds vibrate, at reduced amplitude. The amplitude of vibration at the tip of reeds is high enough for a distint indication.
  • The Pointer Type Frequency Meter has a clear, well defined scale marking at 90 degree angle. The pointer indicates the applied frequency when voltage is applied across the terminals of the meter.

General Specifications

Accuracy ±1.5 / 2.0 of FSD
Measurable Quantities AC and DC Voltage or Current
Pointer deflection 0 - 90º
Frequency 50/60Hz
Sensitivity 1000Ω/V (Voltmeter); 2000Ω/V (ammeter)
Overload Capacity According to IS: 1248 / IEC 51
Short duration for voltmeter 2 times for 5s: 1 overload
2 times for 0.5s: 9 overload
Short duration for ammeter 10 times for 5s: 1 overload
10 times for 5s: 9 overload
Continiously 1.2 times rated voltage or current
Operating Temperature -10 to 55°C
Storage Temperature -25 to 65°C
Relative Humidity < 75% annaul average, non-condensing

Range Chart

Model Description Ammeter
SF - 72, 96 Reed Type 45-50-55 HZ,    47-50-53 HZ,    55-60-65 HZ
SP - 72, 96 Pointer Type 45-50-55 HZ,    47-50-53 HZ,    55-60-65 HZ

Dimensions